Why Kitchen Gas Interlocks Trip When It Turns Cold

2 hours ago
9 min read

Kenny, one of our commercial catering engineers, sent Darren a voice note back in August with a prediction. "When it cools down towards the end of September, October, the grease that's been nice and soft and moist ends up sticking and clogging into the motors." He expected the autumn to be full of faulty fan motors, pressure switches and current monitors in commercial kitchens.

It's worth planning for. If your kitchen gas has started cutting out mid-service, or won't come on at all on a cold morning, the cause may well be up in the extraction. Here's how the interlock system works, why the colder months catch it out, and what you and your team can do about it.

What does a gas interlock do?

A gas interlock links the gas supply in your kitchen to the mechanical ventilation. If the extract fan stops or the airflow drops, the interlock shuts off the gas to the cooking appliances.


Commercial kitchen cook line with gas ranges on both sides under stainless steel extraction canopies

The HSE explains why in its information sheet Gas safety in catering and hospitality (CAIS23). Cooking generates "products of combustion, heat etc", and those have to be carried away. The sheet warns that "if a mechanical system fails or is not working correctly, the environment may become unsafe or unfit for work."

The HSE's guidance is that the installer "should have fitted the appropriate interlocking system between any mechanical ventilation system and the operation of gas appliances". The point is "so that failure of the ventilation system causes the gas supply to the appliances to be shut off."

In plain terms, no extraction means no gas. It protects your staff from breathing in fumes the canopy can no longer clear, and carbon monoxide is the biggest worry among them. Our guide to gas leaks and carbon monoxide covers the symptoms every kitchen manager should know.

The main parts of an interlock system

Systems vary by make and age, but most share the same building blocks.

  • A control panel, usually near the kitchen entrance or the cook line, with start, stop and reset controls.

  • An airflow sensor, either a pressure switch that measures air movement in the duct or a current monitor that reads how hard the fan motor is working.

  • A gas solenoid valve on the supply to the appliances. It stays shut unless the panel tells it to open.

  • Emergency stop buttons so staff can kill the gas quickly.

  • The fans themselves, both extract and, where fitted, the supply fan bringing fresh air in.

Some systems also include gas proving, a check that confirms the pipework holds gas before the supply is opened, and others add air quality monitoring. Your engineer can tell you exactly what's fitted to yours.

Why do interlock faults pick up in autumn?

Kenny's point comes down to fat.

Through the summer, grease in a hot kitchen stays soft. Plenty of it gets carried up into the canopy and the ductwork as vapour and droplets. While the weather is warm it stays runny. It drips back down, or it sits as a soft film that doesn't trouble the fan much.

Then the temperature drops. Darren put it simply when he passed Kenny's message on. "In the summer the fat in the fryers and the cookers melts, and when you go into the colder season it stops melting and the fans and the burners start seizing up."

Cold grease hardens. It builds up on fan blades and around motor housings, and it can coat the small tubes and sensors that read the airflow. A fan that's working harder against a sticky build-up turns more slowly or draws more current than it should. A pressure switch that's partly blocked can misread the airflow.

The interlock does exactly what it was designed to do. It sees a problem with the ventilation, and it shuts off the gas.

From the kitchen side, it feels like the system has failed. In reality the safety system is working and the extraction behind it needs attention. That's why Kenny expected September and October to be "rammed with faulty motors, pressure switches, current monitors". He expects the same pattern through the winter.

Why it shows up at the worst time

Interlock trips can land at peak service. When every burner and fryer is running, the kitchen produces the most heat and grease, and the extraction is under the most strain. A fan that coped at half load can't keep up at full load, so the panel trips just as the orders stack up.

First thing in the morning is the other common time. A cold building, cold grease and a fan starting from a standstill can be enough to stop the system proving airflow.

Which parts fail first?

Kenny named the components our engineers expect to see in autumn and winter, and the gas valve can fail too.

Fan motors

Grease on the impeller and around the motor adds load and builds heat. Bearings wear faster, and a motor that has been labouring for weeks can eventually seize. Sometimes a clean and a service bring it back, and sometimes the motor needs replacing.

Pressure switches

These read the difference in air pressure that a working fan creates. If the sensing tubes clog with grease, or the switch itself gets coated, it can report low airflow when the fan is actually running. You get a trip with no obvious reason.

Current monitors

Where a system watches the fan's electrical current, a struggling motor can push the reading outside the set limits. The panel treats that as a fan fault and cuts the gas.

Gas solenoid valves

The valve that opens and shuts the gas supply can also stick or fail over time. If the panel shows everything healthy but the gas still won't flow, the valve is one of the first things we check.

What are the signs of an interlock or extraction fault?

Most kitchens notice one of these before anything else.

  • The gas won't come on at the start of the day, even with the fans running.

  • The system cuts out during busy periods and needs resetting.

  • The extract fan sounds louder, rougher or slower than usual.

  • The kitchen feels hotter or smokier than normal at full load.

  • The panel shows a fault light that keeps coming back after a reset.

Any one of these is worth a call. The HSE's advice is that anyone with concerns about their gas installation "should not wait until the next routine maintenance visit or breakdown". Get a qualified gas engineer to look at it promptly.

Is it ever OK to bypass an interlock?

No. We understand the pressure when a full restaurant is waiting and the gas has just cut out. Even so, wedging a switch, linking out a sensor or jumping the panel puts your staff at risk.

The HSE is direct about it. "Installation of manual bypasses to such interlock systems is not permitted."

If we find an interlock that's been bypassed, we'll explain the risk and put it right. An engineer can also classify an installation as At Risk or Immediately Dangerous under the industry's unsafe situations procedure. The HSE's sheet is clear that in either case the advice is not to use the appliance or installation.

The quicker way back to cooking is a proper repair. A stuck sensor or a seized fan motor is a known fault with a known fix.

What can your kitchen team do to prevent problems?

A lot of interlock trouble can be headed off with good housekeeping before the cold weather sets in.

Keep on top of canopy filters

Canopy filters are the first line of defence against grease reaching the fans and ductwork. Set a cleaning schedule that matches how hard your kitchen works, and stick to it. A busy fryer kitchen will need filters cleaned far more often than a café doing light lunches.

Get the ductwork cleaned by a specialist

Filters catch a lot, but they don't catch everything. The HSE tells kitchens to "clean ductwork regularly to prevent build-up of grease and fat", and admits the job is unpleasant and often skimped. Ductwork cleaning is specialist work in its own right. Booking it before autumn is a good habit.

Train staff on the panel

Make sure everyone who opens up knows how the interlock panel works, what a normal start looks like and what to do when it trips. HSE guidance says all catering staff who use gas equipment should be trained in how to use it.

Report changes early

A fan that sounds different or a reset that's needed more than usual is an early warning. Getting it looked at during a quiet afternoon is far better than losing a Saturday night.

What if your kitchen doesn't have an interlock?

Older kitchens sometimes don't. The HSE sheet says BS 6173, the British Standard for gas-fired catering appliances, "provides installers with general design information on this subject". It also notes that the standard isn't retrospective, and its message to older kitchens is "do not be complacent."

For kitchens without an interlock, the HSE's advice is to "assess whether a risk is likely to arise" and, where one does, to prevent or control it. In practice that's a conversation with a commercial catering gas engineer about your ventilation and your appliances.

It also ties into the wider legal duty on businesses. Under Regulation 35 of the Gas Safety (Installation and Use) Regulations 1998, employers and the self-employed must keep gas appliances, installation pipework and flues at a workplace under their control "maintained in a safe condition". If you're planning a refit or adding appliances, that's the right time to look at an interlock.

What happens when we come out?

Every visit starts with the fault in front of us. We check the panel and its fault history, then work back through the system. That means the fans, the airflow sensors, the current monitoring, the solenoid valve and the gas supply to the appliances.

Once the fault is found and fixed, we prove the system works the way it should. That includes checking the gas shuts off when the ventilation fails. If your annual inspection is due, we can carry it out at the same visit. Our commercial gas safety certificate page sets out what that covers.


Two DD Wilson engineers standing beside wall-hung commercial boilers and insulated pipework in a plant room

Interlocks, extract fans and the appliances under the canopy all sit within our commercial catering gas engineers service. That covers range cookers, fryers and forced draught burners on natural gas and LPG. For heating plant and other gas work in business premises, see our commercial gas engineers page.

Our earlier post on commercial catering gas safety for Liverpool hospitality goes further into inspections and records. You can also read about how our commercial gas engineers work across heating and gas systems.

Which kitchens do we work with?

Restaurants, cafés, takeaways, pubs and school kitchens can all run into the same autumn pattern. Our North West gas engineers page shows where we work, our full list of services covers everything else we do, and you can read what other business customers say in our commercial testimonial. We've also written about our commercial gas work in Cheshire and Liverpool.

Frequently asked questions

How much does it cost to fix a kitchen gas interlock fault?

It depends on what has failed, since a blocked pressure switch tube is a very different job from a seized fan motor or a failed solenoid valve. We won't guess at a price before we know the fault. Use our quick quote form or call us and we'll talk it through. Our general FAQs answer common questions about how we price and book work.

Why does my kitchen gas keep cutting out during busy service?

A likely reason is the interlock detecting low airflow from the extraction. At full load the fans are under the most strain, and grease build-up on the fan or the sensors can tip them over the limit. It needs an engineer to find which part is struggling.

Can I bypass the interlock to get through service?

No. HSE guidance says manual bypasses to interlock systems are not permitted. Bypassing it removes the protection against fumes and carbon monoxide building up in the kitchen, so call an engineer instead.

Can I reset the interlock panel myself?

Most panels have a reset button for staff to use, following the manufacturer's instructions. If it trips again soon after, or keeps needing a reset, stop resetting it and get it checked. Repeated trips point to a real fault.

How often should a commercial kitchen interlock be checked?

HSE guidance treats annual inspection as a reasonable minimum, with repairs carried out as needed. We check that interlock systems work correctly as part of a commercial catering gas inspection. Busy kitchens can benefit from an extra check before winter.

Do you clean kitchen ductwork?

We work on kitchen extract fans and interlock systems. Deep cleaning inside the ductwork is a specialist job for a duct cleaning firm. We're happy to advise on how a cleaning schedule fits around your gas safety checks.

Which areas do you cover for commercial kitchen gas work?

We're based in Knowsley and cover Liverpool, Merseyside, Cheshire, North Wales and the wider North West. See our areas we cover page, or contact us if your kitchen is on the edge of that.